Passer-T data acquisition device

PSSRT1
320000,00
RUB
The Passer-T data acquisition device is designed for measuring, monitoring and recording voltage and current signals coming from sensors and other sources, as well as generating output discrete and digital signals for their use in monitoring and control systems of technical facilities.

The device also allows you to register indicators of the quality of electricity.

Scope of application of the device-as a part of measurement systems and diagnostics of electric motors on industrial units.

lwh: 160x103x61 mm

Weight: 340 g

Functions performed
Technical specifications
Input/Output characteristics

Functions performed

  • measurement of current values in effect;
  • measurement of current voltage values;
  • calculation of current and voltage spectra;
  • calculation of current and voltage frequency;
  • calculation of electricity quality indicators;
  • alarm when threshold values are exceeded parameters;
  • measurement of the speed of rotation of the shaft.

Technical specifications

The instrument has 3 analog inputs for current measurement and 3 analog inputs for voltage measurement.
The device has 1 digital input and 2 digital outputs.
The time for setting the operating mode of the device is not more than 30 seconds.
The operating mode is continuous and round-the-clock.
The product must be powered from a 24 V ±5 V DC power source%
The power consumption of the device is not more than 1 O W.
Product weight is not more than 400 grams.
The product's operating temperature range is from -25 to+ 50°C.
According to the type of climatic design, the product corresponds to category C4 according to GOST R52931-2008.
In terms of resistance to atmospheric pressure, the product corresponds to group P1 according to GOST R 52931-2008.
In terms of resistance to sinusoidal vibrations, the product corresponds to group N2 according to GOST R 52931-2008.
The degree of protection provided in accordance with GOST 14254-2015, - IP20.

Input/Output characteristics

Digital inputs:
Pulse frequency measurement range - 0 - 10000 Hz
Logical unit voltage - 12 - 28 V
Logical zero voltage - 0 - 2 V
Minimum pulse duration - 4 microseconds

Analog inputs:
Current measurement channels:
Current measurement range - 0 - 10A
Sample rate - 4000 Hz
Frequency range - 40 - 70 Hz
The limit of permissible reduced error - ± 1 .2%
Voltage measurement channels:
Voltage measurement range - 0 - 400 V
Sample rate - 4000 Hz
Frequency range - 40 - 70 Hz
The limit of permissible reduced error - ±0.3%

Digital outputs:
Switching voltage - 32 V
Switched current - 400 mA
Closed state resistance - 2 ohms